The new SG800/duc is born from the elegance and prestige that has always distinguished BEINAT S.r.l. and from the industrial fitness concept. The device has the capacity of controlling, the presence of various types of gases explosive , toxic. The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to it, but also allows execution of a selfdiagnosis and therefore an AUTOMATIC CALIBRATION, in order to always have the maximum detection accuracy. The probe has a 0 ÷ 20 % L.E.L. linear output, conforming to the 4 ÷ 20mA standard.
ALARM THRESHOLDS:
1st LEVEL, pre-alarm. Set at 13 % of L.E.L. The pre-alarm drives 1 relay
2nd LEVEL, main alarm. Set at 20 % of L.E.L. The alarm drives 1 relay

Power Supply: 12÷24 V. dc ± 10%
Power Demand: 1,5 W max @13,8V
The Pre alarm Relay: 10A SELV
Main Alarm Relays: 10A SELV
Indication: Green LED Normal operation, Red LED
State of Alarm, LED Yellow Fault
Sensor: Catalytic
Input Signal: 4 ÷ 20 mA
Data transmission: Not present
Service Port: Present
1st Alarm Threshold: At 13% of LEL
2nd Alarm Threshold: At 20% of LEL
Test Phase Duration: 90 seconds
Functioning Temperature: -10°C to +50°C
Case degree of Protection: IP65
Compatible control units: whole range
Case and Size: Aluminum 100x100x60
Rod Size: 200x20 mm
Flange Size: 60 mm
Packaging: 160x120x350
Weight: 760 grams about