GS100M BEINAT Toxic and Explosive Gas Detector Control Unit for Industrial use
  • GS100M BEINAT Toxic and Explosive Gas Detector Control Unit for Industrial use
  • GS100M BEINAT Toxic and Explosive Gas Detector Control Unit for Industrial use
  • GS100M BEINAT Toxic and Explosive Gas Detector Control Unit for Industrial use

GS100M Toxic and Explosive Gas Detector Control Unit for Industrial use

Cod. GS100M - Toxic and Explosive Gas Detector Control Unit for Industrial use

Through the connection of 1 remote probe, the GS100M control unit has been designed and built according to European regulations to detect the presence of toxic and/explosive gas.
Thanks to this and its other features, it is suitable for: civil use, industrial use and small underground car parks.
The GS100M control unit has three danger levels:
1st LEVEL, 1st Alarm. This was set to 8 % of L.E.L. (120ppm) for all probes.
2nd LEVEL, 2nd Alarm. This was set at 13% of L.E.L. (200ppm) for all probes.
3rd LEVEL, Main Alarm. This was set at 20 % of L.E.L. (300ppm) for all probes
.Other technical features make this control unit extremely versatile and reliable; for example, by using a series of micro-switches it is possible to:
Select or disable the probe when not installed or faulty;
Select the type of gas to be detected (toxic or explosive);
Choose the relay functioning mode (pulsed or continuous);
Choose selection of the intrinsic safety

Power Supply: 230/240 VAC 50/60 Hz.
Battery power supply: 12 VDC ± 10%
Power Demand: 7W during alarms
The Pre alarm Relay: 10A 250V resistive
Main Alarm Relays: 10A 250V resistive
Max number of probe: 1
Catalytic, Pellistor, Electrochemical, Semiconductor
Explosion alarm threshold: 20 % of L.E.L.
Toxic alarm threshold: From 30 ppm to 300ppm
Input signal: 4 ÷ 20 mA
Accuracy: 1 % FS
Positive Safety: Selectable
Fault output relay ON - OFF
Functioning temperature: -10°C ÷ + 60°C
Functioning humidity: Lower than 90% RH
Degree of protection: I P 4 4
Instal lation: Wall or panel mounted
Size: 144 x 144 x 116
Packaging: 170 x 170 x 120
Weight: 850 grams about


 Scarica la scheda in formato PDF

video VIDEO TUTORIAL: CONNECTIONS

GS100M with solenoid valve N.C. 12 VDC and positive safety »

VIDEO BEINAT2GS100M with solenoid valve N.C. 230 VAC without positive safety »

VIDEO BEINAT3 GS100M with solenoid valve N.C. 230 VAC and positive safety »

VIDEO BEINAT4 GS100M with solenoid valve N.O. 230 VAC »

VIDEO BEINAT5 GS100M probes connection »

GS100M