Page 9 - BX308xp_ENG-Rev3
P. 9

General Functions

?                                Up
       ?

                    ?
Relay: Continuous Impulse        Enter
Positive Safe: ON OFF      Left            Right
Latch Zone 1: ON OFF
Latch Zone 2: ON OFF                   Down

Selecting the functioning mode of the Main Alarm Relay

According to the type of installation, you can select the relay functioning mode.
The relay functioning modes are two: continuous and impulse.
In the “Continuous” position, the relay remains closed until the alarm status continues, or until the alarm
stops.
In the “Impulse” position, the relay remains closed for 20 seconds, and then disenergizes afterwards.

Selection
Use the UP and DOWN buttons to select Relay.

Each time you press “ENTER” the Continuous/Impulse message is changed.
Once you have selected it, use the UP and DOWN buttons to move to the next selection.

Selecting the Positive Safety

According to the type of installation, you can select the Positive Safety function.

Selection
Use the UP and DOWN buttons to select Positive Safety.
Each time you press “ENTER” the ON/OFF message is changed.

In the “ON” position, the Positive safety function is enabled.
In the “OFF” position, the Positive safety function is disabled.
Once you have selected it, use the UP and DOWN buttons to move to the next selection.

Selecting memorisation of Main Alarm

According to the type of installation, you can select the activation or deactivation of the Main Alarm Latching.
By selecting the Latching function, the relay remains closed until the RESET button is pressed.
By unselecting the Latching function, the relay won’t remains closed when the alarm stops.
Note. The memorisation is subdivided in three ways:

          1) Memorisation of single zone
          2) Memorisation of first zone
          3) Memorisation of second zone

Selection
Use the UP and DOWN buttons to select Latching (memorization).
Each time you press “ENTER” the ON/OFF message is changed.

In the “ON” position, the latching function is enabled.
In the “OFF” position, the latching function is disabled.
Once you have selected it, use the UP and DOWN buttons to move to the next selection.

                                                                                                                                                                         Page9